You pull the strainer basket from the coolant distribution unit (CDU) at the quarterly check on a PG25 direct-to-chip loop, and there is a soft brown film across part of its perforated wall. The same week's laboratory report shows a low microbial screen on the bulk coolant and propylene glycol at 23.5 vol%. This is a worked example, not a case from a particular site.
Go by the report and the loop is clean: rinse the basket and refit it. Go by the basket and the film is slime: dose a biocide. Either guess, if wrong, leaves the real cause in the loop. Neither follows yet.
The bottle sampled the fluid, not the film
A bulk sample holds what is suspended in the coolant where and when it is drawn. Organisms living in a film on a strainer, pipe wall or cold plate reach the bottle only when pieces are shed. A CDC sampling protocol for building water pairs a biofilm swab with a bulk sample at each tap or shower, and describes the bulk sample as the water in the pipe plus any material shed from biofilm.
The test method has limits too. If the screen was a culture count, it shows only what grew on the chosen medium; the public summary of ASTM E2694, an ATP method for metalworking fluids, cites an estimate that less than 1% of the species in an environmental sample will form colonies under any given set of growth conditions. Any biocide carried into the bottle can also keep acting until it is neutralised.
So the low result is a fair answer for the fluid in that bottle. It says little about the film.
The glycol result changes the odds
At 23.5 vol%, the coolant is below the 24.5 to 29.5 vol% PG25 range in Table 4 of the Open Compute Project (OCP) guideline for propylene glycol fluids. It is also 25 − 23.5 = 1.5 vol% short of the level above which the same table treats the fluid as bio-static, with no biocide needed. Dow's current guide for its DOWFROST LC fluids puts its own line at 24%: at or above that level, osmotic pressure dehydrates bacteria and fungi; below it, glycol is very biodegradable and the system may be at risk of bacterial contamination. The example sits below both lines.
The worry is a loop without its bio-static margin. That makes a biofilm plausible, not proven.
If water is what lowered the reading, the number also says how much got in. The share of today's fluid that is added water is 1 minus today's reading divided by the earlier one: 1 − 23.5 ÷ 24.5 = 0.04 from the bottom of the PG25 range, 1 − 23.5 ÷ 25 = 0.06 from 25 vol%. That is about 4 to 6 litres in every 100 litres of loop. Use your own earlier reading on the same basis (OCP notes that weight percent runs about 0.5 to 1.0 above volume percent), then check the top-up log. Water the log cannot explain points to unlogged top-ups or leftover flush water.
A brown film has more than one explanation
One explanation is a biofilm the bottle under-represents. The others are just as ordinary: a precipitate from poor-quality top-up water, corrosion product, fabrication debris or cleaning residue left in a new or modified loop, or a material that does not suit the fluid. The OCP guideline says sediment, debris or particulates may point to material incompatibility, corrosion or equipment problems, to be investigated before filtering or filling the system with new fluid.
The low glycol fits both stories: whatever water diluted the loop took away its bio-static margin, and poor-quality water would bring in hardness minerals as well.
Check the rest of the report first
The bottle that gave the low screen may also have given results that bear on the film, and they are already paid for.
| On the bulk report | What an out-of-line value points to |
|---|---|
| Hardness, chloride, sulfate | Poor-quality water in the loop, by the notes to OCP's Table 4. Dow's in-use limit for its DOWFROST LC fluids is below 25 ppm for each (hardness as CaCO3). |
| Iron, copper | Metal in the circulating fluid. Dow's in-use limit for its DOWFROST LC fluids is below 5 ppm for each. |
| Appearance and sediment | Solids travelling in the fluid, not only sitting on the basket. |
| Glycol on earlier reports | When the loop dropped below its bio-static level. |
Values in range do not clear the film: like the microbial screen, they describe the fluid. Ask the laboratory which method the screen used and what number sits behind "low". OCP's own lists of report tests include no microbial test; its check for biocontamination is at the filters, so the strainer is the right place to look.
Sample the deposit before you clean the basket
Do not rinse the basket yet. If the unit must run, fit a clean spare and bag the fouled one. Call the laboratory the same day and agree the method, containers and handling, including how long the samples can wait: on the VeriFluid test list, a microbial screen is a specialist test arranged on those terms. Then, in order:
- Photograph the basket before anything touches the film, and note where the film sits.
- Swab the film into a sterile tube and scrape some deposit into a clean container, as the laboratory instructs.
- Ask for the deposit to be split: part for a microbial screen, part for chemical tests the laboratory confirms it can run on a deposit, such as iron, copper, zinc, aluminium and hardness.
- Draw a fresh bulk sample at the same visit, from a point with good circulation, not a dead leg, before any dosing, flushing or top-up. Note whether the strainer had already been opened.
- Open any finer filter on the loop too: the same film there is a second deposit sample.
- Say whether a biocide or other additive has gone into the loop, so the laboratory can neutralise any biocide and interpret the result.
- Send the glycol result, top-up dates and volumes, the date the basket was last cleaned, and a bottle of the top-up water itself for hardness, chloride and sulfate.
Read the results together
The glycol result already calls for action: OCP says fluid outside the PG25 range should be replaced or, in larger systems, adjusted on the fluid supplier's advice. The deposit decides what must happen before new fluid goes in.
| What the deposit shows | What it supports |
|---|---|
| A clear biological signal, little mineral or metal | A biofilm the bulk screen missed. Ask the fluid supplier about cleaning before the fluid change. |
| Mostly hardness minerals, iron or copper, little biological signal | A chemistry or materials source. Check the top-up water, corrosion results and wetted materials first. |
| Both | Treat both. Give the fluid supplier all the results before anyone chooses a cleaner or biocide. |
| Little of either | Something these tests do not see, such as lubricant, cleaning residue or a material that does not suit the fluid. Ask what else the laboratory can run on the deposit, and list what changed on the loop since the basket was last clean. |
Each wrong guess has its own cost. Trust the bulk result and the film can keep growing on surfaces the bottle never samples, and refilling first skips the investigation OCP asks for. Assume microbes without evidence and the obvious next step is a biocide the fluid supplier has not approved, while a water or corrosion source carries on. OCP leaves additives to the fluid supplier, after analysis of a system sample.
The strainer did its job and caught something. Send the laboratory that material with the bottle, and decide on both results.
References
- Open Compute Project, Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Single-Phase Cold Plate-Based Liquid Cooled Racks: PG25 range, bio-static note and weight and volume percent note (Table 4, page 19), poor-quality water notes for hardness, chloride and sulfate (Table 4 notes, page 20), filter checks including biocontamination (section 4.4, page 14), replacing out-of-range fluid and investigating sediment before filtering or refilling (section 6.1, page 18), report test lists (section 6.2, page 18), supplier-recommended additives (sections 2.2 and 6.3, pages 10 and 20).
- Dow, DOWFROST LC Heat Transfer Fluids Engineering and Operating Guide, Version 9/01/2026 (Form No. 971-00014-01-0926): bio-static conditions at 24% glycol or more and the risk of bacterial contamination below it (section 2.3, page 3), fabrication debris, lubricants, cleaning media and residual flush water (section 4.1, page 9), representative samples away from dead legs (section 5.1, page 10), in-use limits for copper, iron, total hardness, chloride and sulfate (Table 9, page 10).
- Centers for Disease Control and Prevention, Sampling Procedure and Potential Sampling Sites: a biofilm swab and a bulk sample at each tap or shower, what the bulk sample captures, and neutralising residual disinfectant in each sample (page 3). Written for building water systems.
- ASTM E2694-26, Measurement of Adenosine Triphosphate in Water-Miscible Metalworking Fluids: public Significance and Use text, section 5.5.1, on the estimated share of species that form colonies under a given set of growth conditions.